Part Number: ETI0001-1450
Rugged Mil Spec 2000 VA Rackmount
Ultra Compact Tactical Integrated UPS
and Intelligent Power Distribution Unit Combination
US Navy Q-70
Tactical Open Systems E-CDWS Standard
Rugged Mil Spec 2000 VA Rack Mount PowerStation Isolated UPS
Ultra Compact 12" Depth, PFC Input, Intelligent PDU
Remote Shutdown and Auxiliary DC Output
ETI0001-1450 Rugged Mil Spec UPS and PDU Standard Front
Panel Layout with 2U Battery Module
ETI0001-1450 Rugged Mil Spec UPS and PDU Standard Rear
Panel Layout with 2U Battery Module
N5 Standard Remote
Panel Optional
N5 Remote Panel w/ EPO
The field proven Rugged Systems™ UPS line is ideally suited for military,
industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.
These units are equally suited for use in shipboard, airborne, vehicular, field
deployed or fixed locations with controlled or uncontrolled environments. The
ETI0001-1450 is specifically designed
as an ultra compact unit to mount
in the Q-70 E-CDWS racks.
The ETI0001-1450 does not require a separate PDU since the PDU
functions are already integrated into the UPS module. This saves rack space,
cabling and expense while improving overall reliability.
The heavy-duty chassis occupies only
4U (7”) for the electronics module and 2U (3.5") for the battery module of
rack space by an ultra shallow 12" deep. The
rounded metal corners and rugged handles, both front and rear, aid in safe
handling. Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration.
The internal shielded
input transformer provides galvanic isolation with provisions for domestic (115
VAC, CONUS) and optional international (230 VAC, OCONUS) input
voltages.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. The input
circuit breaker and the galvanic isolation transformer
all provide a double pole isolated source for all installations including shipboard systems or
overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to
the unit's status including load and battery levels. The high intensity audible alarm can
be heard in high noise environments.
All controls and protective devices are brought to front and rear panels with critical
switches having finger guards. Further, all front panel devices are recessed to prevent
damage or accidental operation. The internal intelligent PDU allows control of
the individual output circuits incorporating thermal and interlock interfaces
for additional control and safety, plus Battleshort override. The display and
control panel can be mounted remotely in the rack at eye level, or on the keyboard console,
or on the unit front panel with only a logic level cable connection.
The rear panel provides locking
connectors for the input and output power with various optional configurations
available. The removable and washable intake air filters and high capacity
stainless steel ball
bearing fan provide added protection in both controlled and hostile environments. This
version draws air through the rear and exhausts out the front vents. The external
battery connector allows the safe and easy addition of the standard or extra battery modules
without having to shut the unit down.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the Battery
Technology section. The Status connectors provide both a contact and
asynchronous serial interface with optional computer
software providing loss of AC and low battery status as well as remote shut down
capability. Besides the standard ETI0001-N5
Series features, the "ETI0001-1450" also has a remote shutdown interface and
an auxiliary DC output. The PDU Remote Control connector provides an
interface to standard or optional remote display/control panels.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N3 Series UPS section for UPS without
the integrated PDU and remote control.
Overall, the PowerStation line is uniquely qualified for critical shipboard, vehicle,
airborne or land based systems combining advanced modular design features with highly
reliable construction.
AC OUTPUT |
Output voltage: |
120 VAC true sinewave standard,
others
optional |
Output rating: UPS |
2000 VA standard in 4U x 12" chassis
0.65 to 0.75 pf standard, optional configurations to 24,000 VA |
Non-linear load capacity: |
Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
Output frequency: UPS |
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available
400 or 1000 Hz output available as an option |
Operational status |
Status, load and battery level LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT |
Input voltage selection: |
Nominal 115 VAC, optional
autoranging input of 85-270 VAC |
Input voltage tolerance: UPS |
85-155 VAC @ full load without
using battery, to 70 VAC @ 75% load |
Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
Input power factor: |
Better than 99% typically |
Input/output isolation: |
2000 VA, up to 120 dB common mode,
<5 mA leakage |
Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
Input control/protection: |
Guarded 3 pole input breaker w/ UPS fuse |
Input power connection: |
AMP MCPC 7-pin Type XII threaded
locking |
EXTERNAL BATTERY |
Battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
Battery life: |
Rated for continuous service life of 5 years |
DC protection: |
Front panel mounted fuse |
Battery expansion: |
Up to 24 hours w/ Battery Expansion Modules |
DISTRIBUTION PANEL |
Output circuits: |
Six controlled outputs via solidstate relays |
Output control: |
Local/remote control panel w/rocker switches
Thermal and remote interlock ON/OFF control |
Output receptacles: |
IEC-320R w/cord restraints |
MECHANICAL |
Dimensions ( H x D x W ):
UPS
2U Battery Module |
7.0 (4U) x 12.5 x 19.0 in (178 x
318 x 483 mm)
3.5 (2U) x 12.5 x 19.0 in (89 x 318 x 483 mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices patterns
standard, others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable, Horizontal/Vertical |
Shipping weight:
UPS
2U Battery Module |
88 lb. (40 kg) with lift handles
front
66 lb. (30 kg) with lift handles front and rear |
Audible noise: |
Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: |
High capacity, positive pressure, forced air |
Cooling air direction: |
Rear intake, exhaust to front |
Air intake filter: |
Washable filter media, various porosities |
ENVIRONMENTAL |
Storage temperature: |
-40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: |
32° to 113° F ambient (0° to 45° C
),
lower/ higher optional |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m) |
Operating elevation: |
Up to 15,000 ft (4,572 m), higher optionally |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D, 1399-300A & 2000 |
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC Part 15, Class A;
EN55022; MIL
STD 461 |
OPTIONAL ACCESSORIES |
|
Autoranging International Input, Cold Start, Alternate I/O Configurations, Dual Source
Input, Battery Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power Distribution Units, Software Interface, Asynchronous serial
COM port, 10BaseT Ethernet SNMP/HTTP port,
Transport Cases, Slides and Mounting Kits |
:
November 23, 2011 |